P1590 - False Voltage Alerts for SPARC Enterprise Mx000 (XSCF) Systems
Dec 16, 2014Patch for BMC Performance Manager Express for Hardware - Version(s) 2.7.26,2.7.28,2.9.00,2.9.10,2.9.20
Download File
Patch content
Connector for SPARC Enterprise Mx000 (XSCF)
Should you install this patch?
Install this patch if you are getting false voltage alerts due to incorrect thresholds.
What does it fix?
- The 1.2V and 12V sensors were assigned the same device ID, resulting in a 12V voltage instance having a 1.2V threshold.
- Negative voltage sensors, such as -12V, are now discovered.
How to install the patch?
- Copy the following file to %RSM_HOME%\RSMxx\SEN_HW\hdf_2xxx\ on each RSM:
- MS_HW_SunXscf.hdf
- No further actions are required. The new component monitoring will be added at the next discovery.